What Washington's code asks for
Washington's residential code, WAC 51-51-0408, requires a ground cover in a vented crawl space: six-mil black polyethylene or an approved equal, over the ground, lapped at the joints and run to the foundation wall. Clear plastic does not meet that wording.
With a Class I vapor retarder over the ground, the same section lets the vent area drop from 1 square foot per 300 square feet of floor to 1 per 1,500, as long as cross ventilation remains. Below the 1-in-300 ratio, the code calls for a radon vent starting under the cover. A fully sealed crawl space with no vents is a different design, covered on our encapsulation page. In each case the City's building official confirms how the code applies to your house.